Т – Three-phase transformer
Д – With natural oil circulation and forced air circulation
Т – Three-winding
Н – Voltage regulation under load (РПН)
Х – Rated power, kVA
150 – HV class, kV
У1 or УХЛ1 – Climatic version and placement category according to ГОСТ 15150
| Technical specifications of ТДТН-16000÷63000/150-У1(УХЛ1) transformers | ||||
|
Parameter name |
Value | |||
|
Transformer type |
ТДТН | |||
|
Rated power, kVA |
16000 | 25000 | 40000 | 63000 |
|
Rated voltage of HV winding, kV |
158 | |||
|
Rated voltage of MV winding, kV |
38,5 | |||
|
Rated voltage of LV winding, kV |
6,6 (11,0) | |||
|
Winding connection diagram and vector group |
Ун/Ун/Д-0-11 (Ун/Д/Д-11-11) | |||
|
No-load losses, kW |
19 | 28,5 | 39 | 55 |
|
Short-circuit losses, kW |
93 | 145 | 200 | 285 |
| Short-circuit voltage HV-MV, % | 10,5 | 10,5 | 10,5 | 10,5 |
| Short-circuit voltage HV-LV, % | 17,5 | 18 | 18,5 | 19 |
| Short-circuit voltage MV-LV, % | 6,5 | 6,5 | 7,0 | 7,5 |
|
No-load current, % |
0,6 | 0,5 | 0,6 | 0,5 |
| Overall dimensions, mm | ||||
|
L - length |
6400 | 6342 | 7200 |
6900 |
|
B - width |
3800 | 3981 | 4800 | 4950 |
|
H - height |
6200 | 5055 | 6600 | 6150 |
|
Oil weight, kg |
14000 | 14000 | 24500 | 21500 |
|
Transport weight, kg |
43500 | 48050 | 75000 | 85000 |
|
Total weight, kg |
50000 | 56100 | 83000 | 98300 |