| Technical Specifications - 110 | |
| Parameter | Value |
| Primary voltage, V |
110000/√3
|
| Secondary voltages, V |
100/√3; 100
|
|
Maximum operating voltage, kV
|
126
|
|
Accuracy classes of measuring windings
|
0,2; 0,5; 1,0; 3,0
|
|
Accuracy classes of protection windings
|
3Р; 6P
|
|
Rated secondary loads
|
- |
|
Measuring windings, V∙A
|
10; 30; 50; 75; 100; 120; 150; 200; 300
|
|
Protection windings, V∙A
|
до 300
|
| Additional winding, V∙A | до 300 |
| Rated frequency, Hz | 50 |
| Weight, max, kg | 695 |
| Oil weight, kg | 165 |
| Dimensions, mm | 410x1825 |
Climatic design О1 according to ГОСТ 15150-69, range: -60 to +55 °C.
Altitude above sea level, m: 1000/2000/3000.
|
Technical Specifications - 220
|
|
|
Parameter
|
Value
|
| Primary voltage, V
|
220000/√3
|
|
Secondary voltages, V
|
100/√3; 100
|
|
Maximum operating voltage, kV
|
252
|
|
Accuracy classes of measuring windings
|
0,2; 0,5; 1,0; 3,0
|
|
Accuracy classes of protection windings
|
3Р; 6P
|
|
Rated secondary loads
|
- |
| Measuring windings, V∙A
|
10; 30; 50; 75; 100; 120; 150; 200; 300
|
|
Protection windings, V∙A
|
до 300
|
| Additional winding, V∙A | до 300 |
| Rated frequency, Hz | 50 |
| Weight, max, kg | 785 |
| Oil weight, kg | 130 |
| Dimensions, mm | 600х3370 |
Climatic design О1 according to ГОСТ 15150-69, range: -60 to +55 °C.
Altitude above sea level, m: 1000/2000/3000.