Power range: 10,000÷16,000 kVA.
Primary winding voltage (HV): 36.75; 35 kV.
Climatic version: У1 or
УХЛ1.
T – Transformer
D – With natural oil circulation and forced air circulation.
N – Equipped with on-load tap changing (РПН).
S – Intended for operation in the auxiliary power systems of power plants.
H – Rated power, kVA.
35 – Voltage class, kV.
У1 or УХЛ1 – Climatic version and placement category according to ГОСТ 15150.
| Technical specifications of ТДНС-10000÷16000/35-У1(УХЛ1) energy-efficient transformers with reduced losses | ||||||||
|
Transformer type |
Rated power, kVA |
Rated voltage, kV | Winding connection diagram and vector group |
Losses, kW |
Short-circuit voltage, % |
No-load current, % |
||
| HV | LV |
No-load |
Short-circuit | |||||
|
ТДНС-10000/35 |
10000 | 36,75 | 10,5; 6,3 | Ун/Д-11 |
11,5 |
60,0 |
8,0 |
0,75 |
|
ТДНС-16000/35 |
16000 | 36,75 | 10,5; 6,3 | Ун/Д-11 |
17,0 |
85,0 |
10 |
0,70 |
| Overall dimensions of ТДНС-10000÷16000/35-У1(УХЛ1) transformers | ||||||||||||
|
Transformer type |
Dimensions, mm |
Weight, kg |
||||||||||
|
L |
B | H |
H1 |
H2 | H3 | A | N | K |
Total
|
Transport | Oil | |
|
ТДНС-10000/35 |
4125 |
3265 |
3685 |
1935 |
550 |
995 |
1524 |
1000 |
300 |
19430 | 16260 | 4100 |
|
ТДНС-16000/35 |
4470 |
3415 |
3922 |
2135 |
585 |
850 |
1524 |
1000 |
400 |
26000 | 22145 | 5250 |
By clicking the “Calculate” button, you consent to the processing of personal data.
Your name
Phone