Т – Three-phase transformer
М – Oil-cooled with natural circulation of oil and air
Х – Rated power, kVA
35 – Voltage class, kV
У1 or УХЛ1 – Climatic version and placement category according to ГОСТ 15150
| Technical specifications of ТМ-1000÷6300/35-У1 (УХЛ1) transformers with reduced losses | ||||||||
|
Transformer type |
Rated power, kVA |
Rated voltage, kV | Winding connection diagram and vector group |
Losses, kW |
Short-circuit voltage, % |
No-load current, % |
||
| HV | LV |
No-load |
Short-circuit | |||||
|
ТМ-1000/35 |
1000 | 35 | 6,0 | У/Д-11 |
2,0 |
11,6 |
6,5 |
1,2 |
|
ТМ-1600/35 |
1600 | 35 | 6,3 | У/Д-11 |
2,75 |
18,0 |
6,5 |
1,0 |
|
ТМ-2500/35 |
2500 | 35 | 10,0 | У/Д-11 |
3,9 |
23,5 |
6,5 |
0,8 |
|
ТМ-4000/35 |
4000 | 35 | 10,5 | У/Д-11 |
5,6 |
33,5 |
7,5 |
0,5 |
|
ТМ-6300/35 |
6300 | 35 | 11,0 | У/Д-11 |
8,0 |
46,5 |
7,5 |
0,3 |
|
Overall dimensions of transformers type
ТМ-1000÷6300/35-У1(УХЛ1)
|
||||||||||||||
|
Transformer type |
Overall dimensions, mm
|
Weight, kg | ||||||||||||
|
L
|
B
|
H
|
H1
|
H2
|
H3
|
M
|
M
|
M |
b
|
b1 | Total | Transport | Oil | |
|
ТМ-1000/35
|
2520
|
1400
|
2760
|
1545
|
280
|
470
|
400
|
1070
|
200 |
215
|
210 | 4380 | 4260 | 1320 |
|
ТМ-1600/35
|
2735
|
1620
|
3020
|
1760
|
280
|
470
|
400
|
1070
|
200 |
220
|
235 | 5320 | 5100 | 1500 |
|
ТМ-2500/35
|
3280
|
2120
|
2945
|
1860
|
280
|
470
|
400
|
1070
|
200 |
240
|
280 | 7350 | 6065 | 2250 |
|
ТМ-4000/35
|
2750
|
3230
|
3200
|
2230
|
280
|
725
|
400
|
1594
|
240 |
245
|
285 | 9820 | 7310 | 2550 |
|
ТМ-6300/35
|
2900
|
3250
|
3480
|
2505
|
280
|
725
|
400
|
1594
|
240 |
260
|
310 | 12790 | 9435 | 3110 |