Quvvat diapazoni: 25000–63000 kVA
Birlamchi o‘ram YuK Yuqori kuchlanishi: 158 kV
Ikkinchi o‘ram
O’K O’rtacha kuchlanishi: 38,5 kV
Iqlim talqini: U1 yoki UHL1
T – Uch fazali transformator
D – Tabiiy moy aylanishi va majburiy havo aylanishi bilan sovitish
T – Uch o‘ramli
N – Yuk ostida kuchlanishni rostlash (RPN)
Х – Nominal quvvat, kVA
150 – YuK Yuqori kuchlanish klassi, kV
U1
ёки UHL1 – ГОСТ 15150 bo‘yicha iqlim talqini va joylashtirish kategoriyasi
| TDTN-25000÷63000/220-U1(UHL1) turidagi transformatorlarning texnik xususiyatlari
|
|||
| Parametr nomi
|
Qiymati | ||
|
Transformator turi
|
TDTN | ||
|
Nominal quvvat, kVA
|
25000 |
40000 |
63000 |
|
Nominal kuchlanish o‘rami YuK (yuqori kuchlanish), kV
|
- | ||
|
Nominal kuchlanish o‘rami O’K (o‘rta kuchlanish), kV
|
38,5 | ||
|
Nominal kuchlanish o‘rami PK (past kuchlanish), kV
|
6,6; (11,0) | ||
|
Chulg‘amlar ulanish sxemasi va guruhi
|
Yn/Yn/D-0-11 | ||
|
Bekor yurishdagi yo‘qotishlar, kW
|
45 | 54 | 65 |
|
Qisqa tutashuvdagi yo‘qotishlar, kW
|
130 | 220 | 285 |
| Qisqa tutashuv kuchlanishi YuK Yuqori kuchlanish- O’K O’rtacha kuchlanish, % | 12,5 | 12,5 | 11,0 |
| Qisqa tutashuv kuchlanishi YuK Yuqori kuchlanish-PK past kuchlanish, % | 20 | 22,0 | 18,5 |
| Qisqa tutashuv kuchlanishi O’K O’rtacha kuchlanish-PK past kuchlanish, % | 6,5 | 9,5 | 6,5 |
| Bekor yurish toki, % | 0,7 | 0,5 | 0,7 |
| O‘lchamlari, mm | |||
| L (uzunlik) | 9600 | 9000 | 8400 |
| B (kenglik) | 5150 | 5350 | 4750 |
| H (balandlik) | 8050 | 7350 | 7200 |
| Yog‘ og‘irligi, kg | 31000 | 35000 | 37400 |
| Tashish og‘irligi, kg | 90000 | 100000 | 105500 |
| To‘liq og‘irlik, kg | 110000 | 115000 | 118500 |