Transformer type ТРДЦН-63000/220-У1 — energy-efficient, with reduced losses.

product
The transformer ТРДЦН-63000/220-У1 is a power, two-winding unit equipped with split LV windings, a bell-type tank, forced air and oil circulation, and on-load tap changing (РПН). The transformer is manufactured for moderate climate conditions and is designed for operation at ambient temperatures from –45°C to +40°C. It features a flat-laminated magnetic core made of high-quality electrical steel. The windings are made of copper conductor. The transformer complies with the requirements of ГОСТ 17544.
Get the cost
Application sent

By clicking the “Calculate” button, you consent to the processing of personal data.

Description

The transformer ТРДЦН-63000/220-У1 is a power, two-winding unit equipped with split LV windings, a bell-type tank, forced air and oil circulation, and on-load tap changing (РПН). The transformer is manufactured for moderate climate conditions and is designed for operation at ambient temperatures from –45°C to +40°C. It features a flat-laminated magnetic core made of high-quality electrical steel. The windings are made of copper conductor. The transformer complies with the requirements of ГОСТ 17544.

Transformer symbols

Т – transformer
Р – split winding
ДЦ – forced air blowing
Н – on-load adjustable
63000 – Rated power, kVA
220 – HV class, kV
У1 – Climatic design and placement category according to ГОСТ 15150

Characteristic

Каталог.cdr


Technical specifications of ТРДЦН-63000/220-У1
 transformer, energy-efficient with reduced losses

Name

Parameters

Climatic design

У1

Ambient temperature

плюс 40°С минус 45°С

Thermal class  

B (category II according to ГОСТ 9920)

Rated power of HV/LV1-LV2 windings, kVA

63000/11-11

Rated voltage of HV winding, V

230000

Rated voltage of LV1-LV2 winding, V

11000-11000

Rated frequency, Hz

50

Number of phases 

3

Winding connection diagram and vector group

Ун/Д-Д-11-11

Type and range of regulation on HV side

РПН in HV neutral ±(12х1,0)%
Switch type RS 9 III 200-123/ К 14273 W or equivalents
External insulation level according to ГОСТ 9920 B ( category II)
No-load losses, kW  70,0
Short-circuit losses, kW 265,0
No-load current, % 0,5
Short-circuit voltage on main tap, relative to rated power in HV-LV mode, % 11,5
Short-circuit voltage on main tap, relative to rated power in HV-LV1(LV2) mode, % 21,0
Short-circuit voltage on main tap, relative to rated power in LV1-LV2 mode, % 28,0
Cooling system type OFAF (ДЦ)
Protection class IP 00
Built-in current transformers: on HV input (two per phase) 600-400-300-200/5
Built-in current transformers: on neutral input (two per phase) 600-400-300-200/5
Roller shape With flange
Control circuit supply voltage of cooling system / OLTC, V Alternating 380/220
Neutral Grounded
Mobility Longitudinal-transverse
Track gauge, mm 1524х3000
Overall dimensions, mm, max length/width/height 8675/4020/6620
230 kV bushings ГКТ II-45-200/2000 01; ГКТ III-60-252/2000 01 ( replacement possible ) Internal insulation — dry type «RIP»
Autocontroller УП-100
Gas relay type BF-80/Q
OLTC drive type МZ-4,4
Oil indicator type МС-2
Transformer oil type   ГК (ВГ)
Transformer weight full / transport / shipping without oil, kg, max 102800/91800/64400
Oil weight, kg, max 27400
Top-up oil, kg, max (not supplied by manufacturer) 3600
Silica gel for thermosiphon filter, kg, max (not supplied by manufacturer) 160
Packing type and transportation method Partial, by rail transport
Seismic resistance points according to MSK-64 8
Cooler type Fans
Creepage distance of external insulation according to ГОСТ 9920, cm/kV Not less than 2,25

Dimensional drawings

print
The transformer ТРДЦН-63000/220-У1 is a power, two-winding unit equipped with split LV windings, a bell-type tank, forced air and oil circulation, and on-load tap changing (РПН). The transformer is manufactured for moderate climate conditions and is designed for operation at ambient temperatures from –45°C to +40°C. It features a flat-laminated magnetic core made of high-quality electrical steel. The windings are made of copper conductor. The transformer complies with the requirements of ГОСТ 17544.
Get the cost
Please fill in all fields with *
Application sent

By clicking the “Calculate” button, you consent to the processing of personal data.

team
Tusov Artem Aleksandrovich
Deputy Director for Marketing and Sales

Can't decide?

Consultation and equipment selection over the phone

Your name

Phone

Your application has been submitted for development
[10]
By clicking the “Request a call” button, you consent to the processing of personal data.