Т – Three-phase. С – Dry З – In protected design Л – With cast insulation. Х – Rated power, kVA. УЗ – Climatic version and placement category according to ГОСТ 15150.
Technical specifications
Parameter name
ТСЗЛ; ТСЛ
Power, kVA
Rated power, kVA
400 630 1000 1600 2500 -HV
6; 10
-LV
0,23; 0,4; 0,69 Winding connection diagram and vector group
У/Ун-0 / Д/Ун-11
Method and range of regulation
ПБВ±2х2,5%
No-load losses, W
1150
1650 2100 2800 4300 Short-circuit losses, W
4300 6400 8750 13500 18400 No-load current, %
1,2 1,0 0,8 0,6 0,4 Short-circuit voltage, %
6 6 6 6 6
|
Overall and installation dimensions of transformers
|
|||||
|
Transformer type
|
Dimensions, mm
|
||||
| L | B | H | |||
|
ТСЛ/ТСЗЛ-400
|
1350/1600
|
850/1195
|
1265/1450
|
||
|
ТСЛ/ТСЗЛ-630
|
1390/1640
|
850/1205
|
1410/1620
|
||
|
ТСЛ/ТСЗЛ-1000
|
1530/1780
|
1000/1245
|
1695/1905
|
||
|
ТСЛ/ТСЗЛ-1600
|
1650/1900
|
1000/1295
|
1975/2185
|
||
|
ТСЛ/ТСЗЛ-2500
|
1840/2090
|
1300/1345
|
2275/2485
|
||