Power range: 63 ÷ 2500 kVA
Т – Three-phase
С – Dry-type
З – Protected design
Х – Rated power, kVA
УЗ – Climatic version and placement category according to ГОСТ 15150
|
Technical Specifications
|
|||||||||
|
Parameter name
|
ТСЗ
|
||||||||
|
Power, kVA
|
|||||||||
|
Rated power, kVA
|
63 | 100 | 160 | 250 | 400 | 630 | 1000 | 1600 | 2500 |
| -
HV
|
6; 10; 10,5
|
6; 10
|
|||||||
| - LV | 0,23; 0,4 | 0,23; 0,4; 0,69 | 0,4; 0,69 | ||||||
|
Winding connection scheme and vector group
|
У/Ун-0
|
У/Ун-0 / Д/Ун-11 | |||||||
|
Regulation method and range
|
ПБВ±5%
|
ПБВ±2х2,5%
|
|||||||
|
No-load losses, W
|
380
|
490
|
700
|
900
|
1200
|
1800
|
2400
|
3100
|
4600
|
|
Short-circuit losses, W
|
1000
|
1500
|
2000
|
3000
|
4200
|
6000
|
9000
|
13000
|
20500
|
|
No-load current, %
|
1,5
|
1,2
|
1,0
|
0,8
|
0,7
|
0,6
|
0,5
|
0,4
|
0,2
|
| Short-circuit voltage, % |
5,5
|
5,5 | 5,5 | 5,5 | 5,5 | 5,5 | 5,5 | 5,5 | 6 |
|
Overall and Installation Dimensions of Transformers
|
|||||
| Rated power, kVA |
Length (L), mm
|
Width (B), mm
|
Height (H), mm
|
Oil mass, kg
|
Total mass, kg
|
| 63 | 800 | 600 | 1100 | 400 | 600 |
| 100 | 1080 | 800 | 1300 | 400 | 800 |
| 160 | 1520 | 925 | 1520 | 660 | 1145 |
| 250 | 1625 | 925 | 1670 | 660 | 1235 |
| 400 | 1755 | 1000 | 1795 | 660 | 1625 |
| 630 | 1925 | 1075 | 1965 | 720 | 2440 |
| 1000 | 2070 | 1100 | 2045 | 760 | 3690 |
| 1600 | 2200 | 1100 | 2350 | 760 | 4995 |
| 2500 | 2640 | 1245 | 2505 | 820 | 7420 |
By clicking the “Calculate” button, you consent to the processing of personal data.